Sensors for the Detection of Incomplete Combustion in Water Heating Boiler Flues
Nemoto’s NAP-78A and NAP-79A catalytic sensors are designed to be fitted to the Exhaust Stacks of water heating boilers to give a warning of dangerous combustion conditions resulting from (for example) a blockage in either the exhaust or inlet stages of the boilers’ flue. Such conditions result in dangerously high levels of Carbon Monoxide in the exhaust line, which is automatically detected by the sensor, enabling a safety shutdown of the boiler, ensuring that the user remains safe from such faults.
Widely used by Japanese boiler manufacturers for many years, recent changes in the European Standard for water heating boilers, EN 483, is resulting in wider acceptance of these devices as an essential safety feature in Water Heating Boilers.
Designed specifically to work reliably within the flue itself for many years, the sensor operates in temperatures up to 260 deg C
|
Detected Gases |
Carbon Monoxide and Hydrogen within boiler flue gas streams |
|
Operational temperature range |
-25°C to +260°C |
|
Recommended Bridge Voltage |
2.0V +/- 0.05V |
|
Zero shift between 23O°C and 200°C |
< +/- 1mV |
|
Typical Output Sensitivity (For a Gas Mixture of 1000ppm CO / 500ppm H2 |
At 23°C: 6mV +/- 1mV At 160°C: 4.8mV+/-0.8mV |
|
Linearity |
Linear to 2% CO |
|
Current Consumption |
< 200 mA @ 2.0V |
|
Response Time (Measured as T90 for a step change from Air to 1000ppm CO / 500ppm H2) |
<60 seconds |
|
Expected Lifetime in the field |
Over 10 Years |
|
|
|
Similar to the NAP-78A, but a less expensive option for those companies wishing to set up their own circuitry arrangements and calibration. Full details of how the use the device is given in the Technical documents (links below)
NAP-78A
Incomplete combustion sensor - Complete pre-calibrated Module
The NAP-78A is a complete module which comprises the catalytic sensor (fitted to the flue) and a separate circuit (fitted in the appliance cabinet) which gives a pre-calibrated zero point - effectively a “Plug and Play” sensor.
NAP-79A
Incomplete Combustion sensor - Sensor only
|
Detected Gases |
Carbon Monoxide and Hydrogen within boiler flue gas streams |
|
Operational temperature range |
-25°C to +260°C |
|
Recommended Bridge Voltage |
2.0V +/- 0.05V |
|
Zero shift between 23O°C and 200°C |
< +/- 1mV |
|
Typical Output Sensitivity (For a Gas Mixture of 1000ppm CO / 500ppm H2 |
At 23°C: 6mV +/- 1mV At 160°C: 4.8mV+/-0.8mV |
|
Linearity |
Linear to 2% CO |
|
Current Consumption |
< 200 mA @ 2.0V |
|
Response Time (Measured as T90 for a step change from Air to 1000ppm CO / 500ppm H2) |
<60 seconds |
|
Expected Lifetime in the field |
Over 10 Years |
|
|
|